Table of Contents
Testing & Acceptance Standards
Rigorous Verification Protocols for Pipeline System Integrity
Acceptance Procedures
Pre-Testing Requirements
All indoor gas pipelines must undergo strength and tightness tests after installation
Test plans and safety measures must be approved by technical and supervision managers
All piping in test scope must be completely installed per design specifications
Pipelines must be properly reinforced for testing
Isolation from non-test systems with clear identification and records
Testing Medium & Equipment
Test medium: Compressed air (water strictly prohibited)
Pressure gauges must be within calibration validity period
Gauge range: 1.5-2 times maximum test pressure
Spring pressure gauge accuracy: 0.4 class
U-tube manometer graduation: ≤1mm
Testing Responsibility
Conducted by construction contractor
Participation required from: Gas operation enterprise, engineering supervision unit, construction unit
Final acceptance organized by construction unit according to project nature
Special Requirements
Buried pipelines must be tested before concealment
Bubble test solution chloride ion content: ≤25×10⁻⁶ for stainless steel systems
Strength Test Specifications
Test Scope Definition
Residential: From inlet pipe valve to gas meter inlet valve (including valves)
Industrial/Commercial: From inlet pipe valve to appliance front valve (including valves)
Pre-valve piping tested together with buried pipelines
Preparation & Pressure Requirements
Pipelines must be purged clean before testing (air or nitrogen only)
Test pressure: 1.5 × design pressure, minimum 0.1MPa
Test Duration & Acceptance Criteria
Design pressure ≥10kPa: Maintain pressure ≥30 minutes, bubble test all joints, no leakage
Alternative: Maintain pressure 60 minutes, no pressure drop
Design pressure <10kPa: Maintain pressure ≥30 minutes, bubble test, no leakage or pressure drop
0.4MPa tests (industrial/commercial): Stop at 1/2 pressure for 15 minutes, bubble check, then continue to full pressure for 60 minutes, no pressure drop
Tightness Test Specifications
Test Scope & Sequence
Scope: All piping from inlet valve to appliance front valve
Additional check required for piping between appliance valve and appliance before commissioning
Must be conducted after strength testing
Medium Pressure Pipelines
Test pressure: Design pressure (minimum 0.1MPa)
Duration: ≥2 hours
Acceptance: Bubble test all connections, no leakage, no pressure drop
Low Pressure Pipelines
Test pressure: Design pressure (minimum 5kPa)
Duration:
Residential: ≥15 minutes
Commercial/Industrial: ≥30 minutes
Systems with stainless bellows/plastic-coated pipes: ≥1 hour
Measurement: U-tube manometer required
Additional check for plastic-coated pipe end seepage
Critical Safety Requirements
Water strictly prohibited as test medium
Safety relief devices must be removed or isolated during strength testing
Proper isolation of non-test systems mandatory
Bubble solution must be promptly cleaned after testing
Low chloride content bubble solution required for stainless steel